|
|
 |
| |
|
| |
SWIMMING POOL SOLAR HEATING
SYSTEM
INSTALLATION MANUAL
|
| |
|
MANUAL SYSTEMS
Some systems can employ a manual control valve to control the flow of
water thru the solar collectors, although this may reduce the overall
heating capacity of the system. The manual control valve usually consists
of a non-positively sealed 3-way valve as shown in Diagram 10. Water continuously
flows through the solar collectors when the filter pump is on, but can
be diverted manually by the pool owner if the pool becomes too warm or
during extended cloudy weather. During a threat of freezing conditions
it can also be diverted, by first shutting off the pool pump, allowing
the collectors to drain, diverting the 3-way manual valve to the bypass
collector position and shutting the isolation valves on the collector
feed and return lines. A lower end cap on the collectors or any of the
connecting hoses can be removed to make sure there is no standing water
in the collectors. The filter pump can then be restarted to allow for
normal pool filtration. During normal operation of the system when the
3-way valve is in the bypass collector position all the water
in the collectors should drain back through the 3-way valve (nonpositively
sealed) when the filter pump shuts off. An alternate way to protect against
sudden freezes can be accomplished by running a bypass line (1/8-1/4,
3-6mm) between the collector feed and return line above the isolation
valves, if any. It is possible that a small amount of water may be present
in the collectors when a non-positively sealed 3-way valve is used and
the filter pump is on. If a positively sealed 3-way valve is used, a bypass
line as mentioned above is mandatory to allow for collector drainage.
|
|
AUTOMATIC CONTROL SYSTEMS
The performance of a solar pool heating system can be improved with
the use of an electronic control and motorized 3-way valve. The control
activates the motorized valve and either sends water thru the collectors
for heating (or nocturnal cooling) or automatically bypasses the collectors
when the pool is warm enough or insufficient sunlight is available. Refer
to the manufacturers Instructions Included with the automatic equipment
you use.
|
|
OTHER EQUIPMENT
Some pools employ an automatic pool cleaner. This should be plumbed
before the control valve to assure positive flow to the cleaner at all
times. If the pool uses an automatic chlorinator, this should be plumbed
after the outlet tee on the return to the pool.
|
|
FLOW RATES
| Table B - Flow Rates |
COLLECTOR SIZE |
| |
4x12 |
4x10 |
4x8 |
| Recommended flow rate per collector, gpm/l |
5.0/18.9 |
4.0/15.1 |
3.25/12.5 |
| Minimum flow rate per collector, gpm/l |
3.0/11.4 |
2.5/9.5 |
2.0/7.6 |
| Maximum # collectors per row |
10 |
12 |
14 |
In order to receive optimum results from collectors, the following recommended
flow rates and number of collectors per row should be followed. When the
system is running, all the collectors should feel uniformly cool to the
touch, and there should be no residual air left in the pool return lines.
If either of these two conditions persist, chances are that the flow rates
thru the collectors are inadequate or the system is not properly balanced.
A flow meter can be installed in the collector feed line to check on the
flow rate. If the flow rates are within the limits as shown in Table B,
then the system may not be properly balanced, especially with systems requiring
multiple banks of collectors. Refer to the following section on Special
System Layouts. If the flow rate is below the minimum as shown in the table
above, then the pool pump horse power or pipe size should be increased,
or a booster pump installed in some cases. If the long hoses on the inlet
and outlet piping connections suck in, then slip a piece of
1 1/2 (50mm) pipe into the hose to prevent this. And also, if the
flow rate is excessive (more than 10 GPM/(37.9l ) collector), or if the
system pressure is greater than 30 psi, a bypass line should be installed
between the collector feed and return lines above the 3-way valve to prevent
problems with the collectors and connection hoses. If there is residual
air in the pool return lines and the collectors do feel cool to the touch,
refer to the section concerning the vacuum relief valve test on page 10. |
|
OPTIONAL ISOLATION VALVES
Isolation valves may be installed in the collector piping so that the
pool may be operated while the collectors are being serviced or during
freezing weather. Install a manually operated ball valve in the collector
inlet line and a check valve on the collector return line. Both valves
are available in the Optional Isolation Kit. Make sure that the arrow
on the check valve is pointing away from the collectors, and that the
ball valve and check valve are located as close to the control valve and
outlet T, respectively. For further precautions in warm climates
where pools are operated year round and periodic freezes can occur, a
bypass line (small diameter tubing) can be located above the ball and
check valve so as to prevent any accidental trapping of water in the collectors
by the pool owner. To make sure no water is left in the collectors for
servicing or during freezes, remember that the pool pump should be shut
off, allowing the collectors to drain naturally, before the optional isolation
valves are used.
|
|
|
 |
| |
Home | Privacy | Company | Ordering | Dealers | Email
Us
© Copyright Solar Development,
Inc. 1998-2002 Florida |
|